ONEAC CX Series Power Conditioner, 140 VA - 9.6 kVA

Reliable operation of manufacturing control systems is critical despite the harsh electrical environment in which they must operate. The ONEAC CX Series power-conditioning transformers protect critical equipment from power disturbances and provide other key power functions.
Performance Characteristics
- Nominal Input Voltage: 120, 240, 480 Vac, 50/60 Hz
- Surge Voltage Withstand Capability: ANSI/IEEE C62.41 Category A&B, 6 kV/200 & 500 Amp, 100 kHz ringwave
- Surge and Noise Rejection-Isolation: with unit under power, and ANSI/IEEE C62.41 Category A pulse applied either normal mode (L-N) or common mode (N-G) at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants using a Keytek 711A/J (or equivalent) surge generator and a low-voltage, high sensitivity probe.
- Load Power Factor: 0:3 leading to 0.3 lagging
- Load Regulation Response Time: <2 msec for a 50% change in load
- Interruption Response Time: output voltage will track input voltage in less than 2 msec at power-off and power-on for a single-cycle asynchronous notch.
- Distortion: <1% THD added into a resistive load
- Overload Protection: fuse
- Cooling: convection